NCY 150.0 RF
NCY 150.0 RF
This specification covers round flexible, PVC insulated cables, intended for internal wiring in dry locations.
Read more- Nexans ref. : NCY 150 RF
Description
Description
Standards
-
ProductIEC 60227-5; IEC 60228
-
TestIEC 60332-1-2
Conductor
Plain, annealed, electrolytic flexible copper conductors, complying with the
applicable requirements of IEC 60227-5
Insulation
PVC based thermoplastic material
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Flexible class 5
Conductor material
Plain annealed copper
Conductor shape
Round, shiny, flexible
Insulation
PVC
Dimensional characteristics
Dimensional characteristics
Approximate weight
1480 kg/m
Diameter over insulation
20.0 mm
Nominal conductor diameter
16.4 mm
Nominal insulation thickness
1.8 mm
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
0.129 Ohm/km
Perm current rating in air 30°C
415 A
Rated Voltage Uo/U (Um)
450/750 V
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Usage characteristics
Usage characteristics
Field of application
LV
Flame retardant
IEC 60332-1-2
Installation type
Indoor
Maximum operating temperature (cables)
70 °C
Metric marking
METRIC MARKING
Minimum Bend Radius - Installed
120 mm